MCB Size Calculator

1 for heaters; 0.8 to 0.9 for motors
Suggested minimum MCB rating
n/a
Design current (Ib)n/a
Next size upn/a
Typical curven/a
Load as share of breakern/a

This is a guide only. Breaker selection depends on the cable, installation method and BS 7671. New circuits must be designed and certified by a qualified electrician.

Formula and breakdown

n/a

n/a

n/a

This MCB size calculator works out the design current of a circuit from its load in watts and suggests the smallest standard miniature circuit breaker rating that covers it. It is a planning aid to help you talk to an electrician, not a replacement for a full circuit design.

Quick answer: Divide the load by the voltage and power factor to get the design current, then pick the next standard breaker at or above it. A 3,000 W load at 230 V draws 13.04 A, so the smallest standard MCB is 16 A, provided the cable is rated for at least 16 A.

MCB size example: 3,000 watts at 230 volts gives 13 amps and a 16 amp breaker

What Is an MCB Size Calculator?

An MCB size calculator finds the design current of a circuit, written Ib, and matches it to standard breaker ratings, written In. Under BS 7671 the basic rule is Ib ≤ In ≤ Iz, where Iz is the current-carrying capacity of the cable as installed. The breaker must be big enough for the load and small enough to protect the cable.

How Do You Use the MCB Size Calculator?

  1. Add up the load the circuit will carry at the same time, in watts.
  2. Enter the voltage and choose single or three phase.
  3. Enter the power factor and the type of load, which guides the breaker curve.
  4. Read the design current and the suggested minimum rating.
MCB Size Calculator with example inputs filled in and the results panel

Common Circuits and Typical MCB Ratings

These are typical values seen in UK homes. Your electrician will confirm what suits your installation.

CircuitTypical loadTypical MCBTypical cable
Lightingup to about 1 kW6 A1.0 or 1.5 mm²
Immersion heater3 kW16 A2.5 mm²
Ring final socket circuitvaries32 A2.5 mm² ring
Cookervaries with diversity32 to 40 A6 to 10 mm²
7 kW EV charger7.4 kW32 A (often Type B or C)6 mm² or larger
9.5 kW electric shower9.5 kW40 to 45 A10 mm²

Type B, C or D?

The curve sets how much short surge the breaker tolerates before tripping. Type B suits most domestic circuits. Type C allows bigger inrush currents from motors, transformers and some LED lighting. Type D is for heavy inrush loads. A higher curve also needs a lower earth fault loop impedance to trip fast enough.

Why Not Just Fit a Bigger Breaker?

If a breaker is larger than the cable can safely carry, the cable could overheat before the breaker trips. Replacing a tripping breaker with a larger one without checking the cable is dangerous. Persistent tripping usually means an overload or a fault that needs investigating.

Worked Example: A Garage Heater Circuit

Example: a homeowner in Ipswich wants a dedicated circuit for a 2 kW heater and a 1 kW compressor in a garage.

  1. Total load = 3,000 W at 230 V with a power factor around 0.9 for the compressor share.
  2. Ib = 3,000 ÷ (230 × 0.9) = 14.5 A.
  3. Smallest standard MCB = 16 A, probably Type C for the compressor.
  4. The electrician checks the cable route and length before confirming.

Frequently Asked Questions

What size MCB do I need for 3 kW?

A 3 kW resistive load at 230 V draws about 13 A, so 16 A is the smallest standard rating.

What size breaker for a 7 kW EV charger?

Most 7 kW chargers use a 32 A breaker on a dedicated circuit, often with specific RCD protection.

Can I replace a 32 A MCB with a 40 A one?

Not unless the cable is rated for 40 A in its installation conditions. Ask an electrician.

What is the difference between an MCB and an RCBO?

An RCBO combines an MCB with residual current protection in one device.

Checked November 2026 by the Solaxyra Editorial Team. Sources: IET: BS 7671 Requirements for Electrical Installations, Electrical Safety First: Fuse boxes and consumer units.