Conduit Fill Calculator

Check the internal, not the nominal, size; 20 mm PVC conduit is often about 17 mm inside
From the cable data sheet; a 2.5 mm² single core is about 3.6 mm
A 45% space factor is a common rule for conduit
Conduit fill
n/a
Against your limitn/a
Maximum cables at your limitn/a
Cable area in totaln/a
Conduit internal arean/a

Fill is one check. Bends, run length and cable grouping also affect how many cables you can install. Follow BS 7671 and the manufacturer’s data.

Formula and breakdown

n/a

n/a

n/a

This conduit fill calculator works out how much of a conduit's internal area your cables take up, checks it against a space factor limit and shows the maximum number of cables of that size. It uses the cables' outer diameter and the conduit's internal diameter.

Quick answer: Divide the total cable area by the conduit's internal area. Six cables of 3.6 mm outer diameter fill about 27% of a conduit with a 16.9 mm bore. At a 45% space factor, the same conduit could take up to 9 of those cables, before allowing for bends and length.

Conduit fill example: six 3.6 mm cables in a 16.9 mm bore conduit fill about 27 percent

What Is a Conduit Fill Calculator?

A conduit fill calculator checks that cables will fit in a conduit without being forced in. Overfilled conduit makes pulling cables difficult, can damage insulation and traps heat. The usual check compares the total cross-sectional area of the cables with the internal area of the conduit, often called the space factor.

How Do You Use the Conduit Fill Calculator?

  1. Enter the conduit's internal diameter. Nominal sizes such as 20 mm or 25 mm refer to the outside; the bore is smaller and varies by type.
  2. Enter the overall diameter of one cable from its data sheet.
  3. Enter the number of cables and your fill limit. A 45% space factor is a common rule for conduit.
Conduit Fill Calculator with example inputs filled in and the results panel

Typical Results

At a 45% limit, using typical bores and single-core cable diameters (check your own products):

Conduit (approx. bore)1.5 mm² (3.0 mm)2.5 mm² (3.6 mm)4 mm² (4.2 mm)6 mm² (4.8 mm)
20 mm (16.9 mm)14975
25 mm (21.4 mm)2215118
32 mm (27.8 mm)38261915

Why Is the Limit Below 100%?

Round cables cannot pack together without gaps, and they need room to be drawn in without stretching or scraping. Long runs and runs with several bends need even more room. The factors in the IET On-Site Guide give a more detailed method for straight runs and runs with bends.

Heat and Grouping

Fitting cables is not the only concern. Cables grouped together in a conduit warm each other, so their current-carrying capacity has to be reduced using grouping factors. A conduit that passes the fill check may still need larger cables for the current involved.

Worked Example: Adding Circuits in a Garage

Example: an electrician in Hull wants to run two radial circuits in an existing 20 mm conduit that already holds four 2.5 mm² singles.

  1. Adding 4 more 2.5 mm² singles makes 8 cables of 3.6 mm.
  2. Fill = 8 × 10.2 mm² ÷ 224 mm² = 36%, within 45%.
  3. The run has two bends, so they check the On-Site Guide factors and grouping derating before confirming.

Frequently Asked Questions

What is the maximum fill for conduit?

A space factor of about 45% is widely used as a rule of thumb for conduit.

How many cables fit in a 20 mm conduit?

Roughly 9 single-core 2.5 mm² cables at 45%, depending on the conduit bore and cable diameter.

Does the number of bends matter?

Yes. Bends and long runs make pulling harder, so fewer cables are allowed.

Should I use the nominal or internal conduit size?

The internal diameter, from the manufacturer's data.

Checked November 2026 by the Solaxyra Editorial Team. Sources: IET: On-Site Guide (BS 7671), IET: BS 7671 Requirements for Electrical Installations.