kVA vs kW: What Is the Difference and Why Does It Matter?

This guide explains the difference between kilovolt-amperes and kilowatts for UK and European readers who need to size a generator, a UPS, an inverter or a supply, using 230 V and 400 V examples throughout. Understanding kVA vs kW stops you buying equipment that looks big enough on paper but trips or overheats under a real load.

Quick answer: In kVA vs kW, kW is real power, the part that does useful work such as heating or turning a motor. kVA is apparent power, the total the supply must carry, set by volts times amps. Power factor links them: kW = kVA ร— power factor. At 0.8, a 10 kVA generator gives 8 kW.

kVA vs kW power triangle showing real power, reactive power and apparent power linked by power factor

kVA vs kW: what is the difference?

A kilowatt (kW) measures real power, the energy per second actually turned into heat, light or motion, while a kilovolt-ampere (kVA) measures apparent power, simply the voltage multiplied by the current flowing. In a circuit where voltage and current rise and fall exactly together, the two numbers are equal. In most AC circuits they are not, because some loads draw current that is out of step with the voltage or distorted in shape.

The ratio between them is the power factor, defined as real power divided by apparent power. It is a number from 0 to 1:

  • kW = kVA ร— power factor
  • kVA = kW รท power factor
  • Power factor = kW รท kVA

The third quantity is reactive power, measured in kVAr (kilovolt-amperes reactive). It is energy that sloshes back and forth between the supply and the magnetic or electric fields of a load every cycle without doing useful work. The three form a right-angled “power triangle”: kVAยฒ = kWยฒ + kVArยฒ. So kVA is always equal to or larger than kW, never smaller.

Note that kVA vs kW is a different comparison from kW vs kWh, which is about power versus energy over time. kVA and kW are both rates; neither is an amount of energy, and your household bill is charged in neither of them.

Why are generators, UPS units and transformers rated in kVA?

Generators, transformers and UPS units are rated in kVA because their limit is the current their windings and electronics can carry without overheating, and current depends on kVA, not kW. A cable or winding heats up according to the current through it, whether that current does useful work or not. The maker cannot know what power factor your loads will have, so the safe way to state capacity is volts times amps.

A diesel or petrol generator actually has two limits. The engine limits real power (kW), because only real power burns fuel. The alternator limits apparent power (kVA), because of current. Many generator sellers quote both, often at an assumed power factor of 0.8, so a set labelled 10 kVA would be labelled 8 kW. Check the rating plate rather than assuming that figure, since some small portable generators and inverter generators are rated differently.

A UPS for a computer or router usually shows two ratings too, for example “1,000 VA / 600 W” (example values). You must stay below both. A load of 550 W with a power factor of 0.6 needs about 917 VA, which fits; the same 550 W at a power factor of 0.5 would need 1,100 VA, which does not, even though the watts look fine.

Does the current depend on kVA or kW?

Current depends on kVA: on a 230 V single-phase supply, every 1 kVA draws about 4.35 A, whatever the power factor. This is the point most kVA vs kW comparison pages miss. Two loads using the same kW can draw very different currents if their power factors differ, and it is current that sizes cables, fuses and breakers.

The table shows what a supply rated at 10 kVA can deliver at different power factors. The current is the same in every row, because it is set by the kVA rating; what changes is how much of that capacity becomes useful kW.

Power factorReal power available (kW)Reactive power (kVAr)Current at 230 V single-phaseCurrent at 400 V three-phase
1.010.00.043.5 A14.4 A per line
0.959.53.143.5 A14.4 A per line
0.99.04.443.5 A14.4 A per line
0.88.06.043.5 A14.4 A per line
0.77.07.143.5 A14.4 A per line
0.66.08.043.5 A14.4 A per line

The single-phase current is 10,000 VA รท 230 V. The three-phase current is 10,000 VA รท (โˆš3 ร— 400 V). To run these numbers for your own rating, use the kVA to amps calculator, which handles both single-phase and three-phase supplies.

What power factor do typical loads have?

Purely resistive loads such as kettles, immersion heaters and filament lamps have a power factor of about 1, so their kW and kVA are the same. Motors, transformers and older fluorescent fittings have power factors well below 1. Electronics vary widely: the Wikipedia article on power factor gives about 0.55 to 0.65 for switched-mode power supplies without correction, 0.7 to 0.75 with passive correction, and up to 0.99 with active power factor correction. European rules (EN 61000-3-2) require many consumer products to include some correction, which is why modern computer power supplies usually score well.

  • Heaters, kettles, ovens, electric showers: about 1.0.
  • Modern PC power supplies with active correction: up to about 0.99.
  • Cheap chargers and small power supplies without correction: often 0.55 to 0.65.
  • Induction motors (pumps, compressors, power tools): below 1, and lower still when lightly loaded. Check the motor plate, which often states “cos ฯ†”.

DC circuits have no power factor in this sense: volts times amps is the real power, so kVA is not used for batteries or solar panels on their DC side.

How do you size a generator or UPS using kVA and kW?

Add up the kW of everything that will run at once, add up the kVA (kW รท power factor for each load), and check that both totals sit below the machine’s kW and kVA ratings with some margin. Adding the kVA figures directly gives a slightly high answer, because reactive parts do not add exactly, so it is a safe upper estimate. These steps work from appliance labels:

  1. List each load that may run at the same time and note its watts from the label.
  2. Find or estimate each load’s power factor (1 for heaters; plate value for motors; 0.6 as a cautious example for small electronics without a stated figure).
  3. Work out kVA for each: kW รท power factor.
  4. Total the kW and the kVA separately.
  5. Compare the kW total with the generator’s kW rating and the kVA total with its kVA rating.
  6. Allow extra for motor starting, which can briefly draw several times the running current.

Example: a 5 kVA generator rated 4 kW at 0.8 power factor is to run a 2 kW heater (power factor 1), a 1.1 kW compressor (example power factor 0.75) and a 300 W electronic load (example power factor 0.6). Real power is 2 + 1.1 + 0.3 = 3.4 kW, below 4 kW. Apparent power is 2 + 1.467 + 0.5 = about 3.97 kVA, below 5 kVA. Current at 230 V is about 3,970 รท 230 = 17.2 A. It fits, but the compressor’s start-up surge could still trip it, so check the generator’s surge rating too.

The kVA to kW calculator and the kW to kVA calculator do each conversion for you.

Connecting a generator to a home’s fixed wiring is not a DIY job. It needs a qualified electrician to fit a proper changeover arrangement so the generator can never feed back into the grid, with the work meeting BS 7671 in the UK. Plugging appliances directly into a portable generator’s own sockets, following the maker’s manual, is the only arrangement that avoids this.

Do UK households pay for kVA or kW?

UK households pay for neither directly: domestic bills charge for energy in kWh plus a daily standing charge, as set out in the Ofgem price cap. A home with a poor power factor does not see a reactive power charge on its bill.

Businesses are different, because for them kVA vs kW can show up in the price. Larger commercial and industrial supplies are often agreed as an available capacity in kVA, and the power factor article notes that utilities typically charge extra when a site’s power factor falls below a limit of about 0.9 to 0.95. That is why factories install power factor correction capacitors; you can estimate the kVAr needed with the power factor calculator.

For households, the place kVA vs kW matters is equipment sizing: generators, UPS units, some solar and battery inverters (which often state output in kVA or VA as well as W), and transformers for garden lighting or workshops.

When are kVA and kW the same?

kVA and kW are the same whenever the power factor is 1, which is true for DC circuits and for purely resistive AC loads such as heaters and kettles. A 3 kW kettle on a 230 V supply draws about 13 A and represents about 3 kVA. In that case it does not matter which unit a label uses.

They drift apart as soon as motors, transformers or uncorrected electronics are involved. A rough kVA vs kW rule: if a label or quote gives only kVA and you have mixed loads, assume you can use about 80% of it as kW unless the maker states otherwise. For a UK socket check, the watts to amps calculator lets you enter a power factor so the current comes out right.

Frequently Asked Questions

Is kVA bigger than kW?

kVA is always equal to or bigger than kW for the same load. They are equal when the power factor is 1, as with heaters and DC circuits. For a load with a power factor of 0.8, the kVA is 25% higher than the kW, because kVA equals kW divided by 0.8.

How many kW is a 10 kVA generator?

At the commonly quoted power factor of 0.8, a 10 kVA generator delivers 8 kW of real power. If your loads are mostly heaters with a power factor near 1, the engine’s kW rating becomes the limit, so check the rating plate, which should state both figures.

Why is my UPS rated in VA and watts?

The VA figure is the limit on current through the UPS electronics, while the watts figure is the limit on real power. Your connected load must stay below both. Electronics with a low power factor can hit the VA limit before the watts limit, so add up both.

Does kVA apply to DC?

No. In a DC circuit voltage and current do not alternate, so there is no phase difference and no reactive power. Volts multiplied by amps gives real power in watts directly, which is why batteries and the DC side of solar panels are rated in W or kW.

Can I improve my home’s power factor to save money?

Not on a normal UK household bill. Domestic tariffs charge per kWh plus a standing charge, with no reactive power or kVA charge, so correction equipment would not reduce the bill. Power factor correction pays off mainly for businesses billed on kVA capacity or reactive power.